Specifications |
|
|
Nominal voltage
(V) |
6 |
|
20-hr rate Capacity to
10.5V at 20C (Ah) |
12 |
|
10-hr rate Capacity to
10.8V at 20C (Ah) |
11.1 |
|
|
|
Dimensions |
|
|
Length
(mm) |
151
(1) |
|
Width
(mm) |
50
(1) |
|
Height over terminals
(mm) |
97.5
(2) |
|
Mass
(kg) |
2.05 |
|
|
|
Terminal
Type |
|
|
FASTON - Quickfit /
release (JST where stated) |
6.35 |
|
|
|
Operating
Temperature Range |
|
|
Storage (in fully
charged condition) |
-20C to
+60C |
|
Charge |
-15C to
+50C |
|
Discharge |
-20C to
+60C |
|
|
|
Storage |
|
|
Capacity loss per month
at 20C (% approx.) |
3 |
|
|
|
Case
Material |
|
|
Standard |
ABS
(UL94:HB) |
|
FR version
available |
UL94:V0 |
|
|
|
Charge
Voltage |
|
|
Float charge voltage at
20C (V)/Block |
6.825
(1%) |
|
Float charge voltage at
20C (V)/Cell |
2.275
(1%) |
|
Float Chg voltage tmp
correction factor from std 20C (mV) |
-3 |
|
Cyclic (or Boost)
charge Voltage at 20C (V)/Block |
7.26
(3%) |
|
Cyclic (or Boost)
charge Voltage at 20C (V)/Cell |
2.42
(3%) |
|
Cyclic Chg voltage tmp
correction factor from std 20C (mV) |
-4 |
|
|
|
Charge
Current |
|
|
Float charge current
limit (A) |
No
limit |
|
Cyclic (or Boost)
charge current limit (A) |
3 |
|
|
|
Maximum Discharge
Current |
|
|
1 second
(A) |
360 |
|
1 minute
(A) |
75 |
|
|
|
Impedance |
|
|
Measured at 1 kHz
(m) |
7 |
|
|
|
Design Life &
Approvals |
|
|
EUROBAT Classification:
Standard Commercial |
3 to
5 |
|
Yuasa design life at
20C (yrs) |
up to
5 |
|
VdS
(Germany) |
VdS No: G
194006 |